Cummins C8D5 — 6 kW (7.5 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C8D5
  • Availability: Pre-order

Cummins C8D5 diesel generator set, 50 Hz: 6.6 kW / 8.2 kVA standby and 6 kW / 7.5 kVA prime. Engine X1.3G2, alternator PI044D, PowerStart 500, a basic panel without paralleling.

Designation: C is the Cummins series, 8 the frame size, D diesel and 5 50 Hz. The X1.3G2 engine is inline three-cylinder 1.3 litre, the smallest engine in the range.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 6.6 and 6 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

The sub-100 kW class is decided by arrangement rather than output: indoor or canopied installation, a fuel tank sized for a day of running, noise level and single-side service access. Check whether a canopy is available for this build (factory table: no) and what degree of protection it provides.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 15). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm95 × 91
Compression ratio18.5:1
BMEP, kPa (standby / prime)711 / 672
Piston speed, m/s4.55
Engine oil capacity, L4.5
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)1.54 / 1.87 / 2.31 / 2.86
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)1.40 / 1.70 / 2.10 / 2.60
Exhaust temperature, °C (standby / prime)550 / 530

Source: Cummins specification sheet DS336-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.

Transient response

Maximum single-step load acceptance, kW (% of standby rating)6.6 (100 %)
Voltage dip at maximum step, %8.8
Frequency dip at maximum step, %8.8
Recovery time, voltage / frequency, s2.1 / 2.4

Source: Cummins transient data sheet TD50-550-RevK, 50 Hz; alternator PI044D, control PS0500, excitation Shunt. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.

Noise

Enclosed sound power level LWA, dB(A)85
Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load)58 / 58 / 59
Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load)52 / 53 / 53

Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.


Diesel generator set
Prime power, kW 6
Standby power, kW 6,6
Prime power, kVA 7,5
Standby power, kVA 8,2
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 95 × 91
Fuel consumption 2.86 L/h (full load, standby)
Engine X1.3G2
Generator model PI044D
Canopy no
EU/TAL 15
Main
Control panel type PS0500