Cummins C825D5A diesel generator set, 50 Hz: 660 kW / 825 kVA standby and 600 kW / 750 kVA prime. Engine VTA28G6, alternator HC6G, PowerCommand 3100, extended panel with wider protection.
Designation: C is the Cummins series, 825 the frame size, D diesel and 5 50 Hz. The VTA28G6 engine is V12, 28 litre, mechanical fuel system.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 660 and 600 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The PowerCommand 3100 determines which protections and interfaces are available.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 86). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 139.7 × 139.7 |
| Compression ratio | 13:1 |
| BMEP, kPa (standby / prime) | 2062 / 1874 |
| Piston speed, m/s | 7.6 |
| Engine oil capacity, L | 83 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 40 / 81 / 121 / 162 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 36 / 73 / 110 / 147 |
| Combustion air, m³/min (standby / prime) | 55 / 49 |
| Exhaust flow at rated load, m³/min (standby / prime) | 132 / 120 |
| Exhaust temperature, °C (standby / prime) | 489 / 464 |
| Max exhaust back pressure, kPa | 10.1 |
| Radiator fan load, kW | 19 |
| Heat rejected to room, BTU/min (standby / prime) | 32 700 / 27 795 |
| Dimensions L × W × H, mm, open set | 4 047 × 1 608 × 2 187 |
| Dry weight, kg | 5 771 |
| Wet weight, kg | 6 040 |
Source: Cummins specification sheet DS31-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Transient response
| Maximum single-step load acceptance, kW (% of standby rating) | 660 (100 %) |
| Voltage dip at maximum step, % | 30.4 |
| Frequency dip at maximum step, % | 7.0 |
| Recovery time, voltage / frequency, s | 3.5 / 4.2 |
| Load step with voltage dip limited to 20 %, kW (% of standby rating) | 495 (75 %) |
| Recovery time for that step, s (voltage / frequency) | 2.1 / 2.4 |
Source: Cummins transient data sheet TD50-HHP-RevB, 50 Hz; alternator HC6G, control PCC3100, excitation PMG. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.
Noise
| Enclosed sound power level LWA, dB(A) | 106 |
| Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load) | 77 / 79 / 80 |
| Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load) | 72 / 74 / 75 |
Source: Cummins noise data sheets ND50-CSHHP-RevB / ND50-OSHHP-RevD. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.