Cummins C825D5 — 600 kW (750 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C825D5
  • Availability: Pre-order

Cummins C825D5 diesel generator set, 50 Hz: 660 kW / 825 kVA standby and 600 kW / 750 kVA prime. Engine QSK23G3, alternator HC6G, PowerCommand 2100, extended panel.

Designation: C is the Cummins series, 825 the frame size, D diesel and 5 50 Hz. The QSK23G3 engine is 6-cylinder 23 litre, electronically managed.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 660 and 600 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The PowerCommand 2100 determines which protections and interfaces are available.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 92). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm170 × 170
Compression ratio16:1
BMEP, kPa (standby / prime)2427 / 2268
Piston speed, m/s8.51
Engine oil capacity, L102
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)47 / 87 / 126 / 166
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)43 / 80 / 116 / 151
Combustion air, m³/min (standby / prime)49.3 / 46.8
Exhaust flow at rated load, m³/min (standby / prime)140.1 / 131
Exhaust temperature, °C (standby / prime)550 / 541
Max exhaust back pressure, kPa10.1
Radiator fan load, kW16
Heat rejected to room, BTU/min (standby / prime)20 965 / 19 196
Dimensions L × W × H, mm, open set4 266 × 1 879 × 2 052
Dry weight, kg6 387
Wet weight, kg6 528

Source: Cummins specification sheet DS32-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.


Diesel generator set
Prime power, kW 600
Standby power, kW 660
Prime power, kVA 750
Standby power, kVA 825
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 170 × 170
Dimensions (L×W×H), mm 4 266×1 879×2 052
Dry weight, kg 6387
Weight, kg 6528
Fuel consumption 166 L/h (full load, standby)
Engine QSK23G3
Generator model HC6G
Canopy no
EU/TAL 92
Main
Control panel type 2100

Write to us