Cummins C80D5 — 58 kW (72 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C80D5
  • Availability: Pre-order

Cummins C80D5 diesel generator set, 50 Hz: 64 kW / 80 kVA standby and 58 kW / 72 kVA prime. Engine 4BTA3.9G1, alternator UCI224F, PowerCommand 1301, automatic start with protection.

Designation: C is the Cummins series, 80 the frame size, D diesel and 5 50 Hz. The 4BTA3.9G1 engine is 4-cylinder 3.9 litre turbocharged and aftercooled, mechanical.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 64 and 58 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

The sub-100 kW class is decided by arrangement rather than output: indoor or canopied installation, a fuel tank sized for a day of running, noise level and single-side service access. Check whether a canopy is available for this build (factory table: no) and what degree of protection it provides.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 15). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm102 × 120
Compression ratio16.5:1
BMEP, kPa (standby / prime)1493 / 1352
Piston speed, m/s6
Engine oil capacity, L9.5
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)5 / 8 / 13 / 17
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)5 / 8 / 12 / 15
Combustion air, m³/min (standby / prime)4.3 / 4.2
Exhaust flow at rated load, m³/min (standby / prime)10.7 / 9.98
Exhaust temperature, °C (standby / prime)505 / 475
Max exhaust back pressure, kPa10.2
Radiator fan load, kW2
Heat rejected to room, BTU/min (standby / prime)2 175 / 1 980
Dimensions L × W × H, mm, open set1 950 × 1 046 × 1 221
Dry weight, kg (open / canopy)1 014 / 1 654
Wet weight, kg (open / canopy)1 050 / 1 785

Source: Cummins specification sheet DS15-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.

Noise

Enclosed sound power level LWA, dB(A)94
Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load)67 / 69 / 70
Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load)62 / 63 / 64
Open set average sound pressure at 1 m, dB(A) (at 100 % load)90
Open set sound power level, dB(A) (at 100 % load)106

Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.


Diesel generator set
Prime power, kW 58
Standby power, kW 64
Prime power, kVA 72
Standby power, kVA 80
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 102 × 120
Dimensions (L×W×H), mm 1 950×1 046×1 221
Dry weight, kg 1014
Weight, kg 1050
Fuel consumption 17 L/h (full load, standby)
Engine 4BTA3.9G1
Generator model UCI224F
Canopy no
EU/TAL 15
Main
Control panel type 1301

Write to us

We will reply to info@levrus.ru shortly