Cummins C80D5 diesel generator set, 50 Hz: 64 kW / 80 kVA standby and 58 kW / 72 kVA prime. Engine 4BTA3.9G1, alternator UCI224F, PowerCommand 1301, automatic start with protection.
Designation: C is the Cummins series, 80 the frame size, D diesel and 5 50 Hz. The 4BTA3.9G1 engine is 4-cylinder 3.9 litre turbocharged and aftercooled, mechanical.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 64 and 58 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The sub-100 kW class is decided by arrangement rather than output: indoor or canopied installation, a fuel tank sized for a day of running, noise level and single-side service access. Check whether a canopy is available for this build (factory table: no) and what degree of protection it provides.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 15). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 102 × 120 |
| Compression ratio | 16.5:1 |
| BMEP, kPa (standby / prime) | 1493 / 1352 |
| Piston speed, m/s | 6 |
| Engine oil capacity, L | 9.5 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 5 / 8 / 13 / 17 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 5 / 8 / 12 / 15 |
| Combustion air, m³/min (standby / prime) | 4.3 / 4.2 |
| Exhaust flow at rated load, m³/min (standby / prime) | 10.7 / 9.98 |
| Exhaust temperature, °C (standby / prime) | 505 / 475 |
| Max exhaust back pressure, kPa | 10.2 |
| Radiator fan load, kW | 2 |
| Heat rejected to room, BTU/min (standby / prime) | 2 175 / 1 980 |
| Dimensions L × W × H, mm, open set | 1 950 × 1 046 × 1 221 |
| Dry weight, kg (open / canopy) | 1 014 / 1 654 |
| Wet weight, kg (open / canopy) | 1 050 / 1 785 |
Source: Cummins specification sheet DS15-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Noise
| Enclosed sound power level LWA, dB(A) | 94 |
| Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load) | 67 / 69 / 70 |
| Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load) | 62 / 63 / 64 |
| Open set average sound pressure at 1 m, dB(A) (at 100 % load) | 90 |
| Open set sound power level, dB(A) (at 100 % load) | 106 |
Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.




