Cummins C700D5 diesel generator set, 50 Hz: 565 kW / 706 kVA standby and 512 kW / 640 kVA prime. Engine VTA28G5, alternator HC5F, PowerCommand 3100, extended panel with wider protection.
Designation: C is the Cummins series, 700 the frame size, D diesel and 5 50 Hz. The VTA28G5 engine is V12, 28 litre, mechanical fuel system.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 565 and 512 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The PowerCommand 3100 determines which protections and interfaces are available.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 86). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 140 × 152 |
| Compression ratio | 13.1:1 |
| BMEP, kPa (standby / prime) | 1751 / 1599 |
| Piston speed, m/s | 7.6 |
| Engine oil capacity, L | 83 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 49.00 / 80.00 / 114.00 / 154.00 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 43.00 / 73.00 / 104.00 / 140.00 |
| Combustion air, m³/min (standby / prime) | 52.6 / 49.5 |
| Exhaust flow at rated load, m³/min (standby / prime) | 122.8 / 119.1 |
| Max exhaust back pressure, kPa | 10.2 |
| Radiator fan load, kW | 19.6 |
| Heat rejected to room, BTU/min (standby / prime) | 21 610 / 19 310 |
| Dimensions L × W × H, mm, open set | 4 047 × 1 608 × 1 942 |
| Dry weight, kg | 5 491 |
| Wet weight, kg | 5 760 |
Source: Cummins specification sheet DS30-CPGK-RevC-RevCR; Layout 23077 VTA28 (565 DFGB). Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Transient response
| Maximum single-step load acceptance, kW (% of standby rating) | 565 (100 %) |
| Voltage dip at maximum step, % | 30.0 |
| Frequency dip at maximum step, % | 9.0 |
| Recovery time, voltage / frequency, s | 5.0 / 6.0 |
Source: Cummins transient data sheet TD50-HHP-RevB, 50 Hz; alternator HC5F, control PCC3100, excitation Shunt. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.
Noise
| Enclosed sound power level LWA, dB(A) | 106 |
| Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load) | 77 / 79 / 80 |
| Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load) | 72 / 74 / 75 |
Source: Cummins noise data sheets ND50-CSHHP-RevB / ND50-OSHHP-RevD. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.