Cummins C700D5 — 512 kW (640 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C700D5
  • Availability: Pre-order

Cummins C700D5 diesel generator set, 50 Hz: 565 kW / 706 kVA standby and 512 kW / 640 kVA prime. Engine VTA28G5, alternator HC5F, PowerCommand 3100, extended panel with wider protection.

Designation: C is the Cummins series, 700 the frame size, D diesel and 5 50 Hz. The VTA28G5 engine is V12, 28 litre, mechanical fuel system.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 565 and 512 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The PowerCommand 3100 determines which protections and interfaces are available.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 86). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm140 × 152
Compression ratio13.1:1
BMEP, kPa (standby / prime)1751 / 1599
Piston speed, m/s7.6
Engine oil capacity, L83
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)49.00 / 80.00 / 114.00 / 154.00
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)43.00 / 73.00 / 104.00 / 140.00
Combustion air, m³/min (standby / prime)52.6 / 49.5
Exhaust flow at rated load, m³/min (standby / prime)122.8 / 119.1
Max exhaust back pressure, kPa10.2
Radiator fan load, kW19.6
Heat rejected to room, BTU/min (standby / prime)21 610 / 19 310
Dimensions L × W × H, mm, open set4 047 × 1 608 × 1 942
Dry weight, kg5 491
Wet weight, kg5 760

Source: Cummins specification sheet DS30-CPGK-RevC-RevCR; Layout 23077 VTA28 (565 DFGB). Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.

Transient response

Maximum single-step load acceptance, kW (% of standby rating)565 (100 %)
Voltage dip at maximum step, %30.0
Frequency dip at maximum step, %9.0
Recovery time, voltage / frequency, s5.0 / 6.0

Source: Cummins transient data sheet TD50-HHP-RevB, 50 Hz; alternator HC5F, control PCC3100, excitation Shunt. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.

Noise

Enclosed sound power level LWA, dB(A)106
Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load)77 / 79 / 80
Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load)72 / 74 / 75

Source: Cummins noise data sheets ND50-CSHHP-RevB / ND50-OSHHP-RevD. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.


Diesel generator set
Prime power, kW 512
Standby power, kW 565
Prime power, kVA 640
Standby power, kVA 706
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 140 × 152
Dimensions (L×W×H), mm 4 047×1 608×1 942
Dry weight, kg 5491
Weight, kg 5760
Fuel consumption 154.00 L/h (full load, standby)
Engine VTA28G5
Generator model HC5F
Canopy no
EU/TAL 86
Main
Control panel type 3100