Cummins C38D5 diesel generator set, 50 Hz: 30.4 kW / 38 kVA standby and 28 kW / 35 kVA prime. Engine X3.3G1, alternator PI144H, factory panel code 46023 for large sets; the function set is confirmed by the build data sheet.
Designation: C is the Cummins series, 38 the frame size, D diesel and 5 50 Hz. The X3.3G1 engine is inline 3.3 litre.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 30.4 and 28 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The sub-100 kW class is decided by arrangement rather than output: indoor or canopied installation, a fuel tank sized for a day of running, noise level and single-side service access. Check whether a canopy is available for this build (factory table: no) and what degree of protection it provides.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 15). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 91.4 × 127 |
| Compression ratio | 18.5:1 |
| BMEP, kPa (standby / prime) | 804 / 757 |
| Piston speed, m/s | 6.35 |
| Engine oil capacity, L | 6.5 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 4 / 5 / 7 / 10 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 3 / 4 / 6 / 9 |
| Exhaust temperature, °C (standby / prime) | 600 / 550 |
| Max exhaust back pressure, kPa | 4.75 |
| Dimensions L × W × H, mm, open set | 1 753 × 930 × 1 250 |
| Dimensions L × W × H, mm, canopy | 2 242 × 967 × 1 513 |
| Dry weight, kg (open / canopy) | 745 / 1 105 |
| Wet weight, kg (open / canopy) | 910 / 1 270 |
Source: Cummins specification sheet DS94-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Transient response
| Maximum single-step load acceptance, kW (% of standby rating) | 29.9 (98 %) |
| Voltage dip at maximum step, % | 8.7 |
| Frequency dip at maximum step, % | 7.7 |
| Recovery time, voltage / frequency, s | 2.9 / 4.0 |
Source: Cummins transient data sheet TD50-550-RevK, 50 Hz; alternator P144H1, control PCC1302, excitation Shunt. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.
Noise
| Open set average sound pressure at 1 m, dB(A) (at 100 % load) | 104 |
| Open set sound power level, dB(A) (at 100 % load) | 119 |
Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.