Cummins C350D5 — 256 kW (320 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C350D5
  • Availability: Pre-order

Cummins C350D5 diesel generator set, 50 Hz: 280 kW / 350 kVA standby and 256 kW / 320 kVA prime. Engine NT855G6, alternator HCI4E, PowerCommand 2100, extended panel.

Designation: C is the Cummins series, 350 the frame size, D diesel and 5 50 Hz. The NT855G6 engine is 6-cylinder 14 litre, mechanical fuel system.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 280 and 256 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The PowerCommand 2100 determines which protections and interfaces are available.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 15). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm140 × 152
Compression ratio14:1
BMEP, kPa (standby / prime)1765 / 1600
Piston speed, m/s7.6
Engine oil capacity, L36
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)20 / 36 / 56 / 76
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)20 / 36 / 52 / 69
Combustion air, m³/min (standby / prime)22.5 / 21.7
Exhaust flow at rated load, m³/min (standby / prime)69.4 / 64.3
Exhaust temperature, °C (standby / prime)607 / 574
Max exhaust back pressure, kPa10.2
Radiator fan load, kW8
Heat rejected to room, BTU/min (standby / prime)9 545 / 8 625
Dimensions L × W × H, mm, open set3 549 × 1 100 × 2 078
Dimensions L × W × H, mm, canopy5 110 × 1 563 × 2 447
Dry weight, kg (open / canopy)3 196 / 4 744
Wet weight, kg (open / canopy)3 386 / 5 576

Source: Cummins specification sheet DS25-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.

Transient response

Maximum single-step load acceptance, kW (% of standby rating)280 (100 %)
Voltage dip at maximum step, %18.3
Frequency dip at maximum step, %3.9
Recovery time, voltage / frequency, s1.5 / 2.1

Source: Cummins transient data sheet TD50-550-RevK, 50 Hz; alternator HC44E, control PCC2100, excitation Shunt. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.

Noise

Enclosed sound power level LWA, dB(A)98
Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load)69 / 72 / 72
Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load)64 / 67 / 68
Open set average sound pressure at 1 m, dB(A) (at 100 % load)105
Open set sound power level, dB(A) (at 100 % load)124

Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.


Diesel generator set
Prime power, kW 256
Standby power, kW 280
Prime power, kVA 320
Standby power, kVA 350
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 140 × 152
Dimensions (L×W×H), mm 3 549×1 100×2 078
Dry weight, kg 3196
Weight, kg 3386
Fuel consumption 76 L/h (full load, standby)
Engine NT855G6
Generator model HCI4E
Canopy no
EU/TAL 15
Main
Control panel type 2100