Cummins C350D5 diesel generator set, 50 Hz: 280 kW / 350 kVA standby and 256 kW / 320 kVA prime. Engine NT855G6, alternator HCI4E, PowerCommand 2100, extended panel.
Designation: C is the Cummins series, 350 the frame size, D diesel and 5 50 Hz. The NT855G6 engine is 6-cylinder 14 litre, mechanical fuel system.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 280 and 256 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The PowerCommand 2100 determines which protections and interfaces are available.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 15). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 140 × 152 |
| Compression ratio | 14:1 |
| BMEP, kPa (standby / prime) | 1765 / 1600 |
| Piston speed, m/s | 7.6 |
| Engine oil capacity, L | 36 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 20 / 36 / 56 / 76 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 20 / 36 / 52 / 69 |
| Combustion air, m³/min (standby / prime) | 22.5 / 21.7 |
| Exhaust flow at rated load, m³/min (standby / prime) | 69.4 / 64.3 |
| Exhaust temperature, °C (standby / prime) | 607 / 574 |
| Max exhaust back pressure, kPa | 10.2 |
| Radiator fan load, kW | 8 |
| Heat rejected to room, BTU/min (standby / prime) | 9 545 / 8 625 |
| Dimensions L × W × H, mm, open set | 3 549 × 1 100 × 2 078 |
| Dimensions L × W × H, mm, canopy | 5 110 × 1 563 × 2 447 |
| Dry weight, kg (open / canopy) | 3 196 / 4 744 |
| Wet weight, kg (open / canopy) | 3 386 / 5 576 |
Source: Cummins specification sheet DS25-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Transient response
| Maximum single-step load acceptance, kW (% of standby rating) | 280 (100 %) |
| Voltage dip at maximum step, % | 18.3 |
| Frequency dip at maximum step, % | 3.9 |
| Recovery time, voltage / frequency, s | 1.5 / 2.1 |
Source: Cummins transient data sheet TD50-550-RevK, 50 Hz; alternator HC44E, control PCC2100, excitation Shunt. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.
Noise
| Enclosed sound power level LWA, dB(A) | 98 |
| Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load) | 69 / 72 / 72 |
| Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load) | 64 / 67 / 68 |
| Open set average sound pressure at 1 m, dB(A) (at 100 % load) | 105 |
| Open set sound power level, dB(A) (at 100 % load) | 124 |
Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.