Cummins C33D5 diesel generator set, 50 Hz: 26.4 kW / 33 kVA standby and 24 kW / 30 kVA prime. Engine X3.3G1, alternator PI144G, factory panel code 46023 for large sets; the function set is confirmed by the build data sheet.
Designation: C is the Cummins series, 33 the frame size, D diesel and 5 50 Hz. The X3.3G1 engine is inline 3.3 litre.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 26.4 and 24 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The sub-100 kW class is decided by arrangement rather than output: indoor or canopied installation, a fuel tank sized for a day of running, noise level and single-side service access. Check whether a canopy is available for this build (factory table: no) and what degree of protection it provides.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 15). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 91.4 × 127 |
| Compression ratio | 18.5:1 |
| BMEP, kPa (standby / prime) | 804 / 757 |
| Piston speed, m/s | 6.35 |
| Engine oil capacity, L | 6.5 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 3 / 5 / 6 / 9 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 2 / 4 / 5 / 7 |
| Exhaust temperature, °C (standby / prime) | 600 / 550 |
| Max exhaust back pressure, kPa | 4.75 |
| Dimensions L × W × H, mm, open set | 1 753 × 930 × 1 250 |
| Dimensions L × W × H, mm, canopy | 2 242 × 967 × 1 513 |
| Dry weight, kg (open / canopy) | 710 / 1 070 |
| Wet weight, kg (open / canopy) | 875 / 1 235 |
Source: Cummins specification sheet DS93-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Noise
| Enclosed sound power level LWA, dB(A) | 92 |
| Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load) | 65 / 67 / 68 |
| Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load) | 59 / 61 / 63 |
| Open set average sound pressure at 1 m, dB(A) (at 100 % load) | 104 |
| Open set sound power level, dB(A) (at 100 % load) | 119 |
Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.