Cummins C28D5 — 20 kW (25 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C28D5
  • Availability: Pre-order

Cummins C28D5 diesel generator set, 50 Hz: 22 kW / 27.5 kVA standby and 20 kW / 25 kVA prime. Engine X2.5G2, alternator PI144E, PowerStart 500, a basic panel without paralleling.

Designation: C is the Cummins series, 28 the frame size, D diesel and 5 50 Hz. The X2.5G2 engine is inline 2.5 litre.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 22 and 20 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

The sub-100 kW class is decided by arrangement rather than output: indoor or canopied installation, a fuel tank sized for a day of running, noise level and single-side service access. Check whether a canopy is available for this build (factory table: no) and what degree of protection it provides.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 15). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm91.7 × 127
Compression ratio18.5:1
BMEP, kPa (standby / prime)851 / 768
Engine oil capacity, L6.5
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)1.63 / 3.25 / 4.88 / 6.50
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)1.50 / 3.00 / 4.50 / 6.00
Exhaust temperature, °C (standby / prime)660 / 660
Max exhaust back pressure, kPa3.38
Dimensions L × W × H, mm, open set1 667 × 930 × 1 247
Dimensions L × W × H, mm, canopy2 082 × 930 × 1 448
Dry weight, kg (open / canopy)441,5 / 766,5
Wet weight, kg (open / canopy)605 / 930

Source: Cummins specification sheet DS342-CPGK-RevBR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.

Transient response

Maximum single-step load acceptance, kW (% of standby rating)22 (100 %)
Voltage dip at maximum step, %9.0
Frequency dip at maximum step, %9.8
Recovery time, voltage / frequency, s4.5 / 6.1

Source: Cummins transient data sheet TD50-550-RevK, 50 Hz; alternator PI144E, control PS0500, excitation Shunt. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.

Noise

Enclosed sound power level LWA, dB(A)90
Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load)63 / 64 / —
Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load)58 / 58 / —
Open set average sound pressure at 1 m, dB(A) (at 100 % load)95
Open set sound power level, dB(A) (at 100 % load)111

Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.


Diesel generator set
Prime power, kW 20
Standby power, kW 22
Prime power, kVA 25
Standby power, kVA 27,5
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 91.7 × 127
Dimensions (L×W×H), mm 1 667×930×1 247
Dry weight, kg 441,5
Weight, kg 605
Fuel consumption 6.50 L/h (full load, standby)
Engine X2.5G2
Generator model PI144E
Canopy no
EU/TAL 15
Main
Control panel type PS0500

Write to us