Cummins C275D5 — 200 kW (250 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C275D5
  • Availability: Pre-order

Cummins C275D5 diesel generator set, 50 Hz: 220 kW / 275 kVA standby and 200 kW / 250 kVA prime. Engine QSL9G5, alternator UCD274K, PowerCommand 1301, automatic start with protection.

Designation: C is the Cummins series, 275 the frame size, D diesel and 5 50 Hz. The QSL9G5 engine is 6-cylinder 8.9 litre, electronically managed.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 220 and 200 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The PowerCommand 1301 determines which protections and interfaces are available.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 4g). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm114 × 145
Compression ratio16.8:1
BMEP, kPa (standby / prime)2785 / 2413
Piston speed, m/s7.2
Engine oil capacity, L26.5
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)17 / 30 / 46 / 63
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)14 / 26 / 38 / 53
Combustion air, m³/min (standby / prime)20.3 / 18.7
Exhaust flow at rated load, m³/min (standby / prime)53 / 44.9
Exhaust temperature, °C (standby / prime)560 / 500
Max exhaust back pressure, kPa10.2
Radiator fan load, kW10
Heat rejected to room, BTU/min (standby / prime)10 190 / 8 415
Dimensions L × W × H, mm, open set3 135 × 1 100 × 1 928
Dimensions L × W × H, mm, canopy4 254 × 1 424 × 2 215
Dry weight, kg (open / canopy)2 295 / 3 872
Wet weight, kg (open / canopy)2 347 / 4 511

Source: Cummins specification sheet DS22-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.

Transient response

Maximum single-step load acceptance, kW (% of standby rating)220 (100 %)
Voltage dip at maximum step, %26.9
Frequency dip at maximum step, %22.3
Recovery time, voltage / frequency, s2.4 / 4.7
Load step with voltage dip limited to 20 %, kW (% of standby rating)187 (85 %)
Recovery time for that step, s (voltage / frequency)2.0 / 4.5

Source: Cummins transient data sheet TD50-550-RevK, 50 Hz; alternator UCD274K, control PCC1301, excitation Shunt. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.

Noise

Enclosed sound power level LWA, dB(A)97
Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load)69 / 71 / 71
Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load)64 / 66 / 66
Open set average sound pressure at 1 m, dB(A) (at 100 % load)101
Open set sound power level, dB(A) (at 100 % load)118

Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.


Diesel generator set
Prime power, kW 200
Standby power, kW 220
Prime power, kVA 250
Standby power, kVA 275
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 114 × 145
Dimensions (L×W×H), mm 3 135×1 100×1 928
Dry weight, kg 2295
Weight, kg 2347
Fuel consumption 63 L/h (full load, standby)