Cummins C275D5 diesel generator set, 50 Hz: 220 kW / 275 kVA standby and 200 kW / 250 kVA prime. Engine QSL9G5, alternator UCD274K, PowerCommand 1301, automatic start with protection.
Designation: C is the Cummins series, 275 the frame size, D diesel and 5 50 Hz. The QSL9G5 engine is 6-cylinder 8.9 litre, electronically managed.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 220 and 200 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The PowerCommand 1301 determines which protections and interfaces are available.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 4g). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 114 × 145 |
| Compression ratio | 16.8:1 |
| BMEP, kPa (standby / prime) | 2785 / 2413 |
| Piston speed, m/s | 7.2 |
| Engine oil capacity, L | 26.5 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 17 / 30 / 46 / 63 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 14 / 26 / 38 / 53 |
| Combustion air, m³/min (standby / prime) | 20.3 / 18.7 |
| Exhaust flow at rated load, m³/min (standby / prime) | 53 / 44.9 |
| Exhaust temperature, °C (standby / prime) | 560 / 500 |
| Max exhaust back pressure, kPa | 10.2 |
| Radiator fan load, kW | 10 |
| Heat rejected to room, BTU/min (standby / prime) | 10 190 / 8 415 |
| Dimensions L × W × H, mm, open set | 3 135 × 1 100 × 1 928 |
| Dimensions L × W × H, mm, canopy | 4 254 × 1 424 × 2 215 |
| Dry weight, kg (open / canopy) | 2 295 / 3 872 |
| Wet weight, kg (open / canopy) | 2 347 / 4 511 |
Source: Cummins specification sheet DS22-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Transient response
| Maximum single-step load acceptance, kW (% of standby rating) | 220 (100 %) |
| Voltage dip at maximum step, % | 26.9 |
| Frequency dip at maximum step, % | 22.3 |
| Recovery time, voltage / frequency, s | 2.4 / 4.7 |
| Load step with voltage dip limited to 20 %, kW (% of standby rating) | 187 (85 %) |
| Recovery time for that step, s (voltage / frequency) | 2.0 / 4.5 |
Source: Cummins transient data sheet TD50-550-RevK, 50 Hz; alternator UCD274K, control PCC1301, excitation Shunt. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.
Noise
| Enclosed sound power level LWA, dB(A) | 97 |
| Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load) | 69 / 71 / 71 |
| Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load) | 64 / 66 / 66 |
| Open set average sound pressure at 1 m, dB(A) (at 100 % load) | 101 |
| Open set sound power level, dB(A) (at 100 % load) | 118 |
Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.