Cummins C2750D5 diesel generator set, 50 Hz: 2200 kW / 2750 kVA standby and 2000 kW / 2500 kVA prime. Engine QSK78G9, alternator MVSI804R, factory panel code 46084 for large sets; the function set is confirmed by the build data sheet.
Designation: C is the Cummins series, 2750 the frame size, D diesel and 5 50 Hz. The QSK78G9 engine is V18, 78 litre, electronically managed.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 2200 and 2000 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
Above 1,600 kW this is no longer a containerised unit but a plant with its own foundation, remote radiator and usually parallel operation. Envelope and mass drive the transport scheme and crane capacity on site, and both are taken from the drawing of the specific build.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 92). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 170 × 190 |
| Compression ratio | 15.5:1 |
| BMEP, kPa (standby / prime) | 2375 / 1613 |
| Piston speed, m/s | 9.5 |
| Engine oil capacity, L | 413 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 162.07 / 289.10 / 411.70 / 541.10 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 157.00 / 267.20 / 378.90 / 492.20 |
| Combustion air, m³/min (standby / prime) | 186 / 147 |
| Exhaust flow at rated load, m³/min (standby / prime) | 415 / 326 |
| Max exhaust back pressure, kPa | 6.09 |
| Dimensions L × W × H, mm, open set | 5 668 × 2 313 × 2 300 |
| Dry weight, kg | 19 996 |
| Wet weight, kg | 20 616 |
Source: Cummins specification sheet DS352-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.