Cummins C250D5 diesel generator set, 50 Hz: 200 kW / 250 kVA standby and 182 kW / 227 kVA prime. Engine 6CTAA8.3G9, alternator UCD274J, PowerCommand 1301, automatic start with protection.
Designation: C is the Cummins series, 250 the frame size, D diesel and 5 50 Hz. The 6CTAA8.3G9 engine is 6-cylinder 8.3 litre turbocharged and aftercooled.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 200 and 182 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The PowerCommand 1301 determines which protections and interfaces are available.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 4g). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet (previous version, engine 6CTAA8.3G2)
| Bore × stroke, mm | 114 × 135 |
| Compression ratio | 16.7:1 |
| BMEP, kPa (standby / prime) | 2230 / 1984 |
| Piston speed, m/s | 6 |
| Engine oil capacity, L | 18.9 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 15 / 28 / 42 / 57 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 14 / 27 / 39 / 51 |
| Combustion air, m³/min (standby / prime) | 15.3 / 14 |
| Exhaust flow at rated load, m³/min (standby / prime) | 40.9 / 35.8 |
| Exhaust temperature, °C (standby / prime) | 565 / 548 |
| Max exhaust back pressure, kPa | 10.2 |
| Radiator fan load, kW | 9 |
| Heat rejected to room, BTU/min (standby / prime) | 6 722 / 5 759 |
| Dimensions L × W × H, mm, open set | 2 686 × 1 300 × 1 547 |
| Dimensions L × W × H, mm, canopy | 3 581 × 1 360 × 2 170 |
| Dry weight, kg (open / canopy) | 1 940 / 2 700 |
| Wet weight, kg (open / canopy) | 2 000 / 3 589 |
This sheet describes the previous build (engine 6CTAA8.3G2). The current build uses the engine named in the description above, so request the current sheet for its fuel consumption, dimensions and weight.
Source: Cummins specification sheet DS21-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.