‎+7 (499) 500-24-60
Moscow, Udaltsova St., 81, bldg 2, office 6
RU|EN
0

Cummins C2500D5A — 1800 kW (2250 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C2500D5A
  • Availability: Pre-order

Cummins C2500D5A diesel generator set, 50 Hz: 2000 kW / 2500 kVA standby and 1800 kW / 2250 kVA prime. Engine QSK60G8, alternator P80R, PowerCommand 3201, a panel with paralleling capability.

Designation: C is the Cummins series, 2500 the frame size, D diesel and 5 50 Hz. The QSK60G8 engine is V16, 60 litre, electronically managed.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 2000 and 1800 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

Above 1,600 kW this is no longer a containerised unit but a plant with its own foundation, remote radiator and usually parallel operation. Envelope and mass drive the transport scheme and crane capacity on site, and both are taken from the drawing of the specific build.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 4g). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm159 × 190
Compression ratio14.5:1
BMEP, kPa (standby / prime)2848 / 2575
Piston speed, m/s9.5
Engine oil capacity, L176
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)140 / 252 / 368 / 500
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)133 / 232 / 336 / 446
Combustion air, m³/min (standby / prime)156 / 145.2
Exhaust flow at rated load, m³/min (standby / prime)379 / 344.1
Exhaust temperature, °C (standby / prime)485 / 460
Max exhaust back pressure, kPa6.7
Radiator fan load, kW38
Heat rejected to room, BTU/min (standby / prime)66 000 / 56 100
Dry weight, kg16 690
Wet weight, kg17 217

Source: Cummins specification sheet DS53-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.

Noise

Open set average sound pressure at 1 m, dB(A) (at 110 % load)104
Open set sound power level, dB(A) (at 110 % load)124

Source: Cummins noise data sheets ND50-CSHHP-RevB / ND50-OSHHP-RevD. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.


Diesel generator set
Prime power, kW 1800
Standby power, kW 2000
Prime power, kVA 2250
Standby power, kVA 2500
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 159 × 190
Dry weight, kg 16690
Weight, kg 17217
Fuel consumption 500 L/h (full load, standby)
Engine QSK60G8
Generator model P80R
Canopy yes
EU/TAL 4g
Main
Control panel type 3201

Write to us

We will reply to info@levrus.ru shortly