‎+7 (499) 500-24-60
Moscow, Udaltsova St., 81, bldg 2, office 6
RU|EN
0

Cummins C2250D5 — 1600 kW (2000 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C2250D5
  • Availability: Pre-order

Cummins C2250D5 diesel generator set, 50 Hz: 1800 kW / 2250 kVA standby and 1600 kW / 2000 kVA prime. Engine QSK60G4, alternator P7G, PowerCommand 3201, a panel with paralleling capability.

Designation: C is the Cummins series, 2250 the frame size, D diesel and 5 50 Hz. The QSK60G4 engine is V16, 60 litre, electronically managed.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 1800 and 1600 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

Above 1,600 kW this is no longer a containerised unit but a plant with its own foundation, remote radiator and usually parallel operation. Envelope and mass drive the transport scheme and crane capacity on site, and both are taken from the drawing of the specific build.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 92). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm159 × 190
Compression ratio14.5:1
BMEP, kPa (standby / prime)2544 / 2296
Piston speed, m/s9.5
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)138 / 229 / 328 / 437
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)114 / 200 / 291 / 394
Combustion air, m³/min (standby / prime)144 / 136
Exhaust flow at rated load, m³/min (standby / prime)336 / 311
Exhaust temperature, °C (standby / prime)450 / 430
Max exhaust back pressure, kPa6.7
Radiator fan load, kW29.1
Heat rejected to room, BTU/min (standby / prime)54 030 / 48 080
Dry weight, kg14 863
Wet weight, kg15 510

Source: Cummins specification sheet DS52-CPGK-RevCR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.

Transient response

Maximum single-step load acceptance, kW (% of standby rating)1800 (100 %)
Voltage dip at maximum step, %42.3
Frequency dip at maximum step, %10.7
Recovery time, voltage / frequency, s9.7 / 9.1

Source: Cummins transient data sheet TD50-HHP-RevB, 50 Hz; alternator P7G, control 3201, excitation PMG. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.

Noise

Open set average sound pressure at 1 m, dB(A) (at 110 % load)104
Open set sound power level, dB(A) (at 110 % load)124

Source: Cummins noise data sheets ND50-CSHHP-RevB / ND50-OSHHP-RevD. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.


Diesel generator set
Prime power, kW 1600
Standby power, kW 1800
Prime power, kVA 2000
Standby power, kVA 2250
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 159 × 190
Dry weight, kg 14863
Weight, kg 15510
Fuel consumption 437 L/h (full load, standby)
Engine QSK60G4
Generator model P7G
Canopy no
EU/TAL 92
Main
Control panel type 3201

Write to us

We will reply to info@levrus.ru shortly