Cummins C200D5E diesel generator set, 50 Hz: 160 kW / 200 kVA standby and 146 kW / 182 kVA prime. Engine QSB7G5, alternator UC274H, factory panel code 46054 for large sets; the function set is confirmed by the build data sheet.
Designation: C is the Cummins series, 200 the frame size, D diesel and 5 50 Hz. The QSB7G5 engine is 6-cylinder 6.7 litre, electronically managed.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 160 and 146 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The factory panel code 46054 for large sets; the function set is confirmed by the build data sheet determines which protections and interfaces are available.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 4g). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 107 × 124 |
| Compression ratio | 17.2:1 |
| BMEP, kPa (standby / prime) | 2537 / 2172 |
| Piston speed, m/s | 6.2 |
| Engine oil capacity, L | 15.1 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 15 / 27 / 37 / 45 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 14 / 26 / 34 / 42 |
| Combustion air, m³/min (standby / prime) | 12.72 / 12.3 |
| Exhaust flow at rated load, m³/min (standby / prime) | 35.82 / 34.14 |
| Exhaust temperature, °C (standby / prime) | 561 / 544 |
| Max exhaust back pressure, kPa | 10.2 |
| Radiator fan load, kW | 6.8 |
| Heat rejected to room, BTU/min (standby / prime) | 6 516 / 5 825 |
| Dimensions L × W × H, mm, open set | 2 656 × 1 100 × 1 658 |
| Dimensions L × W × H, mm, canopy | 3 900 × 1 100 × 2 246 |
| Dry weight, kg (open / canopy) | 1 718 / 2 698 |
| Wet weight, kg (open / canopy) | 2 321 / 3 301 |
Source: Cummins specification sheet DS330-CPGK-RevAR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Noise
| Enclosed sound power level LWA, dB(A) | 97 |
| Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load) | 69 / 70 / 70 |
| Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load) | 64 / 65 / 65 |
| Open set average sound pressure at 1 m, dB(A) (at 100 % load) | 101 |
| Open set sound power level, dB(A) (at 100 % load) | 118 |
Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.