Cummins C2000D5 diesel generator set, 50 Hz: 1650 kW / 2063 kVA standby and 1500 kW / 1875 kVA prime. Engine QSK60G3, alternator P7F, PowerCommand 3201, a panel with paralleling capability.
Designation: C is the Cummins series, 2000 the frame size, D diesel and 5 50 Hz. The QSK60G3 engine is V16, 60 litre, electronically managed.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 1650 and 1500 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
In the 700–1,600 kW class the set usually runs prime, so the heat balance matters as much as the electrical rating. Ask the factory for jacket heat, exhaust heat and the permitted ambient temperature — the radiator and the hall layout follow from them.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 92). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 159 × 190 |
| Compression ratio | 14.5:1 |
| BMEP, kPa (standby / prime) | 2386 / 2158 |
| Piston speed, m/s | 9.5 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 119 / 203 / 292 / 393 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 111 / 187 / 267 / 355 |
| Combustion air, m³/min (standby / prime) | 139 / 125 |
| Exhaust flow at rated load, m³/min (standby / prime) | 320 / 295 |
| Exhaust temperature, °C (standby / prime) | 477 / 452 |
| Max exhaust back pressure, kPa | 6.7 |
Source: Cummins specification sheet D-3223d-CPGK. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Transient response
| Maximum single-step load acceptance, kW (% of standby rating) | 1650 (100 %) |
| Voltage dip at maximum step, % | 43.7 |
| Frequency dip at maximum step, % | 19.6 |
Source: Cummins transient data sheet TD50-HHP-RevB, 50 Hz; alternator P7F, control 3201, excitation PMG. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.
Noise
| Open set average sound pressure at 1 m, dB(A) (at 110 % load) | 104 |
| Open set sound power level, dB(A) (at 110 % load) | 124 |
Source: Cummins noise data sheets ND50-CSHHP-RevB / ND50-OSHHP-RevD. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.