Cummins C17D5 diesel generator set, 50 Hz: 13 kW / 16.5 kVA standby and 12 kW / 15 kVA prime. Engine X2.5G2, alternator PI044G, PowerStart 500, a basic panel without paralleling.
Designation: C is the Cummins series, 17 the frame size, D diesel and 5 50 Hz. The X2.5G2 engine is inline 2.5 litre.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 13 and 12 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The sub-100 kW class is decided by arrangement rather than output: indoor or canopied installation, a fuel tank sized for a day of running, noise level and single-side service access. Check whether a canopy is available for this build (factory table: no) and what degree of protection it provides.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 15). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 91.7 × 127 |
| Compression ratio | 18.5:1 |
| BMEP, kPa (standby / prime) | 851 / 768 |
| Engine oil capacity, L | 6.5 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 0.96 / 1.92 / 2.87 / 3.83 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 0.91 / 1.82 / 2.72 / 3.63 |
| Exhaust temperature, °C (standby / prime) | 660 / 660 |
| Max exhaust back pressure, kPa | 3.38 |
| Dimensions L × W × H, mm, open set | 1 667 × 930 × 1 247 |
| Dimensions L × W × H, mm, canopy | 2 082 × 930 × 1 448 |
| Dry weight, kg (open / canopy) | 418,5 / 743,5 |
| Wet weight, kg (open / canopy) | 582 / 907 |
Source: Cummins specification sheet DS338-CPGK-RevBR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Transient response
| Maximum single-step load acceptance, kW (% of standby rating) | 13.2 (100 %) |
| Voltage dip at maximum step, % | 5.1 |
| Frequency dip at maximum step, % | 7.4 |
| Recovery time, voltage / frequency, s | 4.1 / 4.9 |
Source: Cummins transient data sheet TD50-550-RevK, 50 Hz; alternator PI044G, control PS0500, excitation Shunt. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.
Noise
| Enclosed sound power level LWA, dB(A) | 90 |
| Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load) | 63 / 64 / — |
| Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load) | 58 / 58 / — |
| Open set average sound pressure at 1 m, dB(A) (at 100 % load) | 95 |
| Open set sound power level, dB(A) (at 100 % load) | 111 |
Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.