Cummins C175D5E diesel generator set, 50 Hz: 140 kW / 175 kVA standby and 126 kW / 158 kVA prime. Engine QSB7G5, alternator UCI274F, factory panel code 46054 for large sets; the function set is confirmed by the build data sheet.
Designation: C is the Cummins series, 175 the frame size, D diesel and 5 50 Hz. The QSB7G5 engine is 6-cylinder 6.7 litre, electronically managed.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 140 and 126 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The factory panel code 46054 for large sets; the function set is confirmed by the build data sheet determines which protections and interfaces are available.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — IIIA). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Noise
| Enclosed sound power level LWA, dB(A) | 97 |
| Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load) | 69 / 70 / 70 |
| Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load) | 64 / 65 / 65 |
| Open set average sound pressure at 1 m, dB(A) (at 100 % load) | 101 |
| Open set sound power level, dB(A) (at 100 % load) | 118 |
Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.