Cummins C1675D5 diesel generator set, 50 Hz: 1340 kW / 1675 kVA standby and 1120 kW / 1400 kVA prime. Engine KTA50G8, alternator P7D, PowerCommand 2100, extended panel.
Designation: C is the Cummins series, 1675 the frame size, D diesel and 5 50 Hz. The KTA50G8 engine is V16, 50 litre, mechanical fuel system.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 1340 and 1120 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
In the 700–1,600 kW class the set usually runs prime, so the heat balance matters as much as the electrical rating. Ask the factory for jacket heat, exhaust heat and the permitted ambient temperature — the radiator and the hall layout follow from them.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 104). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 159 × 159 |
| Compression ratio | 14.9:1 |
| BMEP, kPa (standby / prime) | 2275 / 1910 |
| Piston speed, m/s | 7.9 |
| Engine oil capacity, L | 178 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 92 / 165 / 253 / 345 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 82 / 155 / 222 / 289 |
| Combustion air, m³/min (standby / prime) | 99.2 / 90.2 |
| Exhaust flow at rated load, m³/min (standby / prime) | 261 / 231 |
| Exhaust temperature, °C (standby / prime) | 510 / 485 |
| Max exhaust back pressure, kPa | 6.7 |
| Radiator fan load, kW | 29.7 |
| Heat rejected to room, BTU/min (standby / prime) | 52 430 / 42 210 |
| Dimensions L × W × H, mm, open set | 5 690 × 2 033 × 2 330 |
| Dry weight, kg | 10 324 |
| Wet weight, kg | 10 626 |
Source: Cummins specification sheet DS46-CPGK-RevCR; Layout 23077 KTA50. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Transient response
| Maximum single-step load acceptance, kW (% of standby rating) | 1340 (100 %) |
| Voltage dip at maximum step, % | 31.1 |
| Frequency dip at maximum step, % | 10.2 |
| Recovery time, voltage / frequency, s | 2.9 / 5.3 |
Source: Cummins transient data sheet TD50-HHP-RevB, 50 Hz; alternator P7D, control PCC2100, excitation PMG. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.
Noise
| Enclosed sound power level LWA, dB(A) | 108 |
| Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load) | 77 / 82 / 83 |
| Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load) | 73 / 79 / 79 |
| Open set average sound pressure at 1 m, dB(A) (at 110 % load) | 109 |
| Open set sound power level, dB(A) (at 110 % load) | 129 |
Source: Cummins noise data sheets ND50-CSHHP-RevB / ND50-OSHHP-RevD. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.