Cummins C1675D5 — 1120 kW (1400 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C1675D5
  • Availability: Pre-order

Cummins C1675D5 diesel generator set, 50 Hz: 1340 kW / 1675 kVA standby and 1120 kW / 1400 kVA prime. Engine KTA50G8, alternator P7D, PowerCommand 2100, extended panel.

Designation: C is the Cummins series, 1675 the frame size, D diesel and 5 50 Hz. The KTA50G8 engine is V16, 50 litre, mechanical fuel system.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 1340 and 1120 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

In the 700–1,600 kW class the set usually runs prime, so the heat balance matters as much as the electrical rating. Ask the factory for jacket heat, exhaust heat and the permitted ambient temperature — the radiator and the hall layout follow from them.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 104). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm159 × 159
Compression ratio14.9:1
BMEP, kPa (standby / prime)2275 / 1910
Piston speed, m/s7.9
Engine oil capacity, L178
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)92 / 165 / 253 / 345
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)82 / 155 / 222 / 289
Combustion air, m³/min (standby / prime)99.2 / 90.2
Exhaust flow at rated load, m³/min (standby / prime)261 / 231
Exhaust temperature, °C (standby / prime)510 / 485
Max exhaust back pressure, kPa6.7
Radiator fan load, kW29.7
Heat rejected to room, BTU/min (standby / prime)52 430 / 42 210
Dimensions L × W × H, mm, open set5 690 × 2 033 × 2 330
Dry weight, kg10 324
Wet weight, kg10 626

Source: Cummins specification sheet DS46-CPGK-RevCR; Layout 23077 KTA50. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.

Transient response

Maximum single-step load acceptance, kW (% of standby rating)1340 (100 %)
Voltage dip at maximum step, %31.1
Frequency dip at maximum step, %10.2
Recovery time, voltage / frequency, s2.9 / 5.3

Source: Cummins transient data sheet TD50-HHP-RevB, 50 Hz; alternator P7D, control PCC2100, excitation PMG. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.

Noise

Enclosed sound power level LWA, dB(A)108
Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load)77 / 82 / 83
Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load)73 / 79 / 79
Open set average sound pressure at 1 m, dB(A) (at 110 % load)109
Open set sound power level, dB(A) (at 110 % load)129

Source: Cummins noise data sheets ND50-CSHHP-RevB / ND50-OSHHP-RevD. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.


Diesel generator set
Prime power, kW 1120
Standby power, kW 1340
Prime power, kVA 1400
Standby power, kVA 1675
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 159 × 159
Dimensions (L×W×H), mm 5 690×2 033×2 330
Dry weight, kg 10324
Weight, kg 10626
Fuel consumption 345 L/h (full load, standby)
Engine KTA50G8
Generator model P7D
Canopy no
EU/TAL 104
Main
Control panel type 2100