Cummins C11D5 diesel generator set, 50 Hz: 8.8 kW / 11 kVA standby and 8 kW / 10 kVA prime. Engine X1.3G2, alternator PI044E, PowerStart 500, a basic panel without paralleling.
Designation: C is the Cummins series, 11 the frame size, D diesel and 5 50 Hz. The X1.3G2 engine is inline three-cylinder 1.3 litre, the smallest engine in the range.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 8.8 and 8 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
The sub-100 kW class is decided by arrangement rather than output: indoor or canopied installation, a fuel tank sized for a day of running, noise level and single-side service access. Check whether a canopy is available for this build (factory table: no) and what degree of protection it provides.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 15). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 95 × 91 |
| Compression ratio | 18.5:1 |
| BMEP, kPa (standby / prime) | 711 / 672 |
| Piston speed, m/s | 4.55 |
| Engine oil capacity, L | 4.5 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 1.10 / 1.70 / 2.40 / 3.30 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 1.50 / 1.90 / 2.30 / 3.00 |
| Exhaust temperature, °C (standby / prime) | 550 / 530 |
Source: Cummins specification sheet DS337-CPGK-RevBR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Transient response
| Maximum single-step load acceptance, kW (% of standby rating) | 8.8 (100 %) |
| Voltage dip at maximum step, % | 6.3 |
| Frequency dip at maximum step, % | 12.5 |
| Recovery time, voltage / frequency, s | 2.8 / 3.4 |
Source: Cummins transient data sheet TD50-550-RevK, 50 Hz; alternator PI044E, control PS0500, excitation Shunt. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.