Cummins C1100D5 diesel generator set, 50 Hz: 888 kW / 1110 kVA standby and 800 kW / 1000 kVA prime. Engine QST30G4, alternator HC6K, PowerCommand 3100, extended panel with wider protection.
Designation: C is the Cummins series, 1100 the frame size, D diesel and 5 50 Hz. The QST30G4 engine is V12, 30 litre, electronically managed.
The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 888 and 800 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.
In the 700–1,600 kW class the set usually runs prime, so the heat balance matters as much as the electrical rating. Ask the factory for jacket heat, exhaust heat and the permitted ambient temperature — the radiator and the hall layout follow from them.
Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 92). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.
Factory data sheet
| Bore × stroke, mm | 140 × 165 |
| Compression ratio | 14:1 |
| BMEP, kPa (standby / prime) | 2544 / 2310 |
| Piston speed, m/s | 8.3 |
| Engine oil capacity, L | 154 |
| Fuel consumption, L/h, standby (¼ / ½ / ¾ / full) | 60 / 107 / 164 / 224 |
| Fuel consumption, L/h, prime (¼ / ½ / ¾ / full) | 54 / 102 / 151 / 202 |
| Combustion air, m³/min (standby / prime) | 60.3 / 56.7 |
| Exhaust flow at rated load, m³/min (standby / prime) | 178.6 / 164.7 |
| Exhaust temperature, °C (standby / prime) | 575 / 565 |
| Max exhaust back pressure, kPa | 6.8 |
| Radiator fan load, kW | 17 |
| Heat rejected to room, BTU/min (standby / prime) | 28 500 / 26 390 |
| Dimensions L × W × H, mm, open set | 4 571 × 1 702 × 2 332 |
| Dry weight, kg | 7 195 |
| Wet weight, kg | 7 374 |
Source: Cummins specification sheet DS36-CPGK-RevCR; Layout 23077 QST30 (888 DFHD). Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.
Transient response
| Maximum single-step load acceptance, kW (% of standby rating) | 888 (100 %) |
| Voltage dip at maximum step, % | 39.7 |
| Frequency dip at maximum step, % | 9.8 |
| Recovery time, voltage / frequency, s | 6.0 / 7.2 |
Source: Cummins transient data sheet TD50-HHP-RevB, 50 Hz; alternator HC6K, control PCC3100, excitation PMG. Factory values for the standard build; voltage dip depends on the alternator, excitation and the type of load, so a project with a large single starting step needs a calculation.