Cummins C1000D5 — 751 kW (939 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C1000D5
  • Availability: Pre-order

Cummins C1000D5 diesel generator set, 50 Hz: 833 kW / 1041 kVA standby and 751 kW / 939 kVA prime. Engine QST30G3, alternator HC6J, PowerCommand 3100, extended panel with wider protection.

Designation: C is the Cummins series, 1000 the frame size, D diesel and 5 50 Hz. The QST30G3 engine is V12, 30 litre, electronically managed.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 833 and 751 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

In the 700–1,600 kW class the set usually runs prime, so the heat balance matters as much as the electrical rating. Ask the factory for jacket heat, exhaust heat and the permitted ambient temperature — the radiator and the hall layout follow from them.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 86). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm140 × 165.1
Compression ratio14:1
BMEP, kPa (standby / prime)2358 / 2117
Piston speed, m/s8.3
Engine oil capacity, L133
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)54 / 98 / 150 / 204
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)51 / 94 / 139 / 184
Combustion air, m³/min (standby / prime)56.2 / 51.8
Exhaust flow at rated load, m³/min (standby / prime)163 / 146
Exhaust temperature, °C (standby / prime)563 / 541
Max exhaust back pressure, kPa10.2
Radiator fan load, kW18.6
Heat rejected to room, BTU/min (standby / prime)22 970 / 21 200
Dimensions L × W × H, mm, open set4 297 × 1 685 × 2 079
Dry weight, kg6 117
Wet weight, kg6 296

Source: Cummins specification sheet DS35-CPGK--RevCR; Layout 23077 QST30 (833 DFHC). Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.

Noise

Enclosed sound power level LWA, dB(A)106
Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load)77 / 79 / 80
Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load)72 / 74 / 75

Source: Cummins noise data sheets ND50-CSHHP-RevB / ND50-OSHHP-RevD. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.


Diesel generator set
Prime power, kW 751
Standby power, kW 833
Prime power, kVA 939
Standby power, kVA 1041
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 140 × 165.1
Dimensions (L×W×H), mm 4 297×1 685×2 079
Dry weight, kg 6117
Weight, kg 6296
Fuel consumption 204 L/h (full load, standby)
Engine QST30G3
Generator model HC6J
Canopy no
EU/TAL 86
Main
Control panel type 3100